Power Distortion Rate : Less Than 1 Percent
Mixing Time : 15s (0 to 999s)
Price : Negotiable
Static Release Time : 900s (0 to 9999s)
Test Function : Insulating Oil Breakdown Voltage
Step Up Speed : 0.5 to 5.0 kV/s
Test Times : 6 Times (1 to 9 Optional)
Brand Name : XZH TEST
Model Number : XHYY102M
Certification : ISO CE
Place of Origin : Xi'an Shaanxi China
MOQ : 1unit
Payment Terms : T/T
Supply Ability : 3000unit/year
Delivery Time : 5-8 work days
Packaging Details : wooden packaging
Voltage Accuracy : 2 Percent Reading Plus 2 Words
Electrode Gap : 2.5 mm Standard
Interval Rest Time : 300s (0 to 999s)
Output Voltage : 0 to 80kV
Booster Capacity : 1.5KVA
XHYY102M Insulating Oil Breakdown Voltage Tester — a high-accuracy, full digital instrument that measures the breakdown voltage of transformer insulating oil up to 80kV, with automatic microcomputer control.
The XHYY102M is a high-accuracy, full digital industrial instrument developed according to the relevant standards and regulations of insulating oil testing. The machine is easy to operate and beautiful in shape; because it uses automatic digital microcomputer control, it delivers high measurement accuracy, strong anti-interference and safe, reliable operation.
Main Functions & FeaturesOne test is run automatically from mixing, through step-up, to breakdown — and the operator can tune each stage. The default values and adjustable ranges are:
| Stage | Default | Adjustable Range |
|---|---|---|
| Mixing time | 15s | 0–999s |
| Step-up speed | 0.5–5.0 kV/s, in 0.5 steps (10 gears) | Error 0.2 kV/s |
| Test times | 6 times | 1–9 times |
| Static release time | 900s | 0–9999s |
| Interval rest time | 300s | 0–999s |
| Electrode gap | 2.5mm standard | — |
The instrument program is equipped with GB/T507-1986, GB/T507-2002, DL429.9, IEC156 and self-programming operation, so a single unit adapts to a wide range of choices from different users.
Technical Data| Booster capacity | 1.5KVA |
| Step-up speed | 0.5–5.0 kV/s (increasing every 0.5), 10 gears optional, error 0.2 kV/s |
| Output voltage | 0–80kV (optional) |
| Voltage accuracy | (2% of reading + 2 words) |
| Power distortion rate | <1% |
| Electrode gap | 2.5mm standard |
| Test times | 6 times (1–9 times optional) |
| Static release time | 900s (0–9999s optional) |
| Interval rest time | 300s (0–999s optional) |
| Mixing time | 15s (0–999s optional) |
| Ambient temperature | 0–40°C |
| Relative humidity | ≤85% |
| Working power | AC 220V (1±10%) |
| Power frequency | 50Hz (1±10%) |
| Power consumption | <200W |
The XHYY102M suits teams that run repeated oil breakdown tests as part of oil handling and maintenance:
With automatic mixing, step-up, rest and release timing, the XHYY102M delivers consistent results across repeated tests. Please contact us for configuration details such as the infrared oil temperature measurement option.
|
|