Sign In | Join Free | My futurenowinc.com |
|
Brand Name : XZH TEST
Model Number : XHHD523L
Certification : CE/ISO
Place of Origin : China
MOQ : 1unit
Payment Terms : T/T
Supply Ability : 1000 units per year
Delivery Time : 5-8 work days
Packaging Details : wooden packaging
Product Description
With the full deployment of the urban network transformation, many power supply bureaus, construction parties, and even design units encountered 110kV XLPE cables for the first time. Due to time constraints and insufficient experience, many cables failed to pass the withstand voltage test (10kV/ 1min). At present, most of the outer sheath is made of HDPE sheath material, which has passed the DC 25kV/5min withstand voltage test in the factory, and the leakage current is as low as tens of μA. Therefore, most of the defects after laying are caused by external force damage during laying, including soil filling and cover. Defects after operation usually include termite bites; water in the grounding box; deterioration of the original defect; moisture penetration of the bifurcated part of the grounding wire reduces the insulation resistance, etc., sometimes because the cable is buried too deep or the surrounding conditions are complicated, so It is very difficult to locate, and some defects cannot be resolved after many years, leaving hidden dangers to the operation. The output voltage of the high-voltage cable outer sheath fault detector is 10KV and below, which fully meets the Chinese national standard GB50150-2006 cable outer sheath withstand voltage test regulations, including the cable outer sheath handovertest and preventive test suitable for cross-interconnect systems And the fault location of the outer sheath of the cable. Quickly and accurately find hidden dangers of 10kv-500kv single-core and three-core high-voltage and ultra-high voltage cable outer sheath grounding faults and large leakage currents. At the same time, it can perform 5kv-10kv on high-density polyethylene and polyvinyl chloride cable outer sheaths, The 1 minute DC withstand voltage test is a special instrument necessary for the maintenance of cable equipment of 10kv-500kv single-core and three-core high-voltage and ultra-high voltage cable operation units, ultra-high voltage cable engineering companies, and various power transmission and trans
Main features
1 with over-current, overvoltage, overheating automatic protection function;
2 It is safer and more reliable with zero start protection;
3 Unique self-discharge design, as long as the high-voltage output is cut off, the high-voltage itself will be zero;
4 with current and voltage double pointer meter display, intuitive and clear;
5. One-key switch between positioning mode and withstand voltage mode, which is convenient and quick;
6 There is no blind spot in the test range;
7. The receiver sensitivity is adjustable, which is more convenient for positioning;
8 Over-current protection switch function, withstanding voltage mode and positioning mode are convenient to use.
Technical data
Input voltage | 220V (±10%), 50Hz (±2Hz); |
Output voltage | 0 ~ 10kV (square wave) adjustable; |
Output current | 0~200mA |
Output capacity | 2kVA; |
Frequency adjustment | Min: 0.2Hz, Max: 5Hz (range adjustable). |
![]() |