| Sign In | Join Free | My futurenowinc.com |
|
Price : Negotiable
Brand Name : XZH TEST
Model Number : XHSB505B
Certification : ISO CE
Place of Origin : Xi'an ShanXi China
MOQ : 1unit
Payment Terms : T/T
Supply Ability : 3000unit/year
Delivery Time : 5-8 work days
Packaging Details : wooden packaging
The XHSB505B Cable Identifier is designed for high-voltage cable construction, installation and maintenance personnel who need a practical way to identify a specific cable among many cables on site. Guided by electromagnetic field theory and built with modern electronic technology and tooling, it delivers fast and accurate cable identification. In power cable laying, relocation, maintenance and fault handling, one of the most troublesome problems is determining which cable is the one you are looking for — especially in cable trenches where many cables of the same specification run together. This device solves that problem quickly and accurately.
Key FeaturesThe transmitter generates a special pulse signal that is applied to the cable to be identified through the connecting line. Based on the principle of electromagnetic induction, a signal consistent with the transmitted signal is induced along the cable. On site, a high-sensitivity receiver clamp combined with the handheld receiver is used to test all cables present, and the target cable (the de-energized cable carrying the injected signal) can be identified accurately from the indication on the handheld receiver.
Live (energized) cable identificationThe transmitter generates a special pulse signal that is applied to one point of the live cable to be identified through the dedicated transmitter clamp. Based on the principle of electromagnetic induction, a signal consistent with the transmitted signal is induced along the cable. On site, a high-sensitivity receiver clamp combined with the handheld receiver is used to test all cables present, and the target cable (the live cable carrying the injected signal) can be identified accurately from the indication on the handheld receiver.
Technical Parameters| Item | Specification |
|---|---|
| Identification Method | Determined by the swing direction of the meter pointer |
| Transmitter Clamp | Φ125 mm |
| Receiver Clamp | Φ200 mm |
| Output Voltage | Position I (direct connection method): 150 V; Position II (coupling method): 250 V |
| Test Range | Direct connection method: 0 Ω – 1 kΩ; Coupling method: 0 Ω – 50 Ω |
| Pulse Current | 0 – 10 A |
| Pulse Period | 2.75 s / time |
| Power Supply | Transmitter: 12 VDC lithium battery; handheld receiver: AA (No. 5) battery |
Transmitter wiring
Cable identification is affected by the grounding condition of the grounding system and by whether the cable shield or armor is intact; the two wiring methods above give the most ideal identification results.
Operating steps
Precautions
Operating steps
The instrument comes with a one-year free warranty for quality problems from the date of purchase, and lifetime repair and technical service are provided. If you find that the instrument is not operating normally or a fault occurs, please contact us so that we can arrange the most convenient and effective solution for you. Service phone: 400-029-0829.
FAQQ1. Can the XHSB505B identify both live and de-energized cables?
Yes. The direct connection method (position "I") is used for de-energized cables, and the coupling method (position "II") is used for live cables. Both methods use the same principle of injecting a pulse signal and reading the indication on the handheld receiver.
Q2. How do I know which of the cables is the target one?
Identification is based on the swing direction of the meter pointer. Only the cable carrying the injected signal shows continuous characteristic signals in the same direction, with a swing frequency consistent with the transmitter, and emits a "beep-beep-beep" sound. Note the arrow direction of the receiver clamp — the arrow points to the far end — otherwise the pointer swings in the opposite direction.
Q3. What should I do if the pointer swings too weakly or irregularly?
If the pointer swing frequency is inconsistent with the transmitter or the swing amplitude is too small, the received signal is too weak: turn the receiver adjustment knob clockwise to increase the received signal strength. If the pointer swings irregularly or not at all, the interference is too strong or the tested cable is not the target cable. When identifying a live cable with severe interference that causes the receiver clamp to magnetically saturate, it is recommended to use the de-energized method.
Q4. Do I need to power off the cable before testing?
Not necessarily. For live cables, use the coupling method: clamp the transmitter clamp directly onto the cable with no operation on the tested cable. Both ends of the cable sheath must be well grounded; if the sheath is not grounded at both ends or is broken in the middle, the coupling method cannot be used and the direct connection method is recommended instead. Also keep the receiver clamp at least 2 m away from the transmitter clamp.
Q5. What is included in the package, and what about after-sales service?
The standard package includes the transmitter, receiver, charger, one red output line, one black output line, one transmitter clamp, one receiver clamp and two AA (No. 5) batteries. The instrument comes with a one-year free warranty for quality problems from the date of purchase, plus lifetime repair and technical service.
|
|
Cable Identification | Energized/De-energized Low-Voltage Power Cable Identifier (Suitable for Field Maintenance) | XHSB505B Images |